RKC 200 C1

  • Duct fan with circular connections.
  • RKC is a converted RK by using a RK-Kit.Proven performance and reliability.
  • Designed to cope with high pressure and long ducts.
  • Impeller with forward curved blades.
  • The external rotor motor has maintenance-free sealed ball-bearings.
  • Integrated motor protection.
  • Junction box has enclosure class IP 54.
  • For speed control a transformer or electronic speed controller can be connected.
  • Fan housing is manufactured from galvanized sheet steel.
  • Swing-out design to simplify maintenance and cleaning of the impeller.
  • The fan is intended to be installed in a duct system.
  • A duct connected fan can be installed outside or in damp environments.
  • Easy installation in any position.
  • To comply with the ErP 2018 regulation, a local demand controller must be used.

Technical Data

RKC 200 C1
7500033+7600001
Parameter Value Unit
Voltage 230 V
Phase 1 ~
Frequency 50 Hz
Power 196 W
Current 0.86 A
Speed 990 r.p.m.
Max. temperature of transported air 40 °C
Max. temperature of transported air when speed controlled 40 °C
Sound pressure level at 3 m 50 dB(A)
Weight 13.5 kg
Enclosure class 44 IP
Insulation class, motor F
Capacitor 6 µF
Max. flow @ 0Pa 220 l/s
Max. pressure 237 Pa
Voltage range 220-240 V

Product information sheet

Parameter Value Unit
(a) Manufacturer Östberg -
(b) Model code RKC 200 C1 -
(c) SEC value -24.3 kWh/m2
  SEC class C -
(d) Declared type NRVU / UVU -
(e) Type of drive Multi-speed drive (accessory) -
(f) Type of heat recovery N/A -
(g) Thermal efficiency N/A %
(h) Max. flow rate (@100Pa) 751 m3/h
(i) Power at max. flow rate 180 W
(j) Sound power level 57 dB LwA
(k) Reference flow rate 0.218 m3/s
(l) Reference pressure difference 50 Pa
(m) SPI 0.24 W/(m3/h)
(n) Type of control/ctrl factor Local demand control -
(o) External (and internal) leakage rate 0.17 (N/A) %
(p) Mixing rate N/A -
(q) Visual filter warning N/A -
(r) Instruction supply/exhaust grilles See manual -
(s) Disassembly instructions fsp.ostberg.com -
(t) Airflow sensitivity N/A -
(u) Air tightness N/A m/s
(v) AEC 160 kWh
(w) AHS average 3018 kWh
  AHS warmer 1365 kWh
  AHS colder 5904 kWh

Accessories

Mechanical accessories