7500047 - | RK 400x200 C3 |
RK 400x200 C3 7500047 |
||
---|---|---|
Parameter | Value | Unit |
Voltage | 400 | V |
Voltage Delta | 230 | V |
Phase | 3 | ~ |
Frequency | 50 | Hz |
Power | 252 | W |
Current | 0.46 | A |
Current Delta | 0.80 | A |
Speed | 1260 | r.p.m. |
Max. temperature of transported air | 80 | °C |
Sound pressure level at 3 m | 49 | dB(A) |
Weight | 13.0 | kg |
Enclosure class | 44 | IP |
Insulation class, motor | F | |
Capacitor | - | µF |
Duct connection | 400x200 | mm |
Max. flow @ 0Pa | 310 | l/s |
Max. pressure | 240 | Pa |
Voltage range | 380-415 | V |
Parameter | Value | Unit |
---|---|---|
(a) Manufacturer | Östberg | - |
(b) Model code | RK 400x200 C3 | - |
(c) Declared type | NRVU / UVU | - |
(d) Type of drive | Multi-speed drive (accessory) | - |
(e) Type of HRS | N/A | - |
(f) Thermal efficiency | N/A | % |
(g) Nominal flow rate | 0.131 | m3/s |
(h) Effective power input | 0.109 | kW |
(i) SFP int | N/A | W/(m3/s) |
(j) Face velocity | 2.3 | m/s |
(k) Nominal external pressure | 240 | Pa |
(l) Internal pressure drop | N/A | Pa |
(n) Static efficiency | 32.2 | % |
(o) External (and internal) leakage rate | 0.3 (N/A) | % |
(p) Filter classification | N/A | - |
(q) Visual filter warning | N/A | - |
(r) Sound power level | 56 | dB LwA |
(s) Disassembly instructions | www.ostberg.com | - |