7880042 - | IRB 160 B1 |
IRB 160 B1 7880042 |
||
---|---|---|
Parameter | Value | Unit |
Voltage | 230 | V |
Phase | 1 | ~ |
Frequency | 50 | Hz |
Power | 59 | W |
Current | 0.26 | A |
Speed | 2580 | r.p.m. |
Max. temperature of transported air | 80 | °C |
Max. temperature of transported air when speed controlled | 80 | °C |
Sound pressure level at 3 m | 37 | dB(A) |
Weight | 11.7 | kg |
Enclosure class | 44 | IP |
Insulation class, motor | F | |
Capacitor | 2 | µF |
Duct connection | 160 | mm |
Max. flow @ 0Pa | 125 | l/s |
Max. pressure | 441 | Pa |
Voltage range | 220-240 | V |
Parameter | Value | Unit |
---|---|---|
(a) Manufacturer | Östberg | - |
(b) Model code | IRB 160 B1 | - |
(c) Declared type | NRVU / UVU | - |
(d) Type of drive | Multi-speed drive | - |
(e) Type of HRS | N/A | - |
(f) Thermal efficiency | N/A | % |
(g) Nominal flow rate | 0.058 | m3/s |
(h) Effective power input | 0.058 | kW |
(i) SFP int | N/A | W/(m3/s) |
(j) Face velocity | 2.9 | m/s |
(k) Nominal external pressure | 271 | Pa |
(l) Internal pressure drop | N/A | Pa |
(n) Static efficiency | 22.9 | % |
(o) External (and internal) leakage rate | 0.47 | % |
(p) Filter classification | N/A | - |
(q) Visual filter warning | N/A | - |
(r) Sound power level | 44 | dB LwA |
(s) Disassembly instructions | www.ostberg.com | - |
IRB 160 B1 7880042 50/60Hz |
||
---|---|---|
Parameter | Value | Unit |
Voltage | 230 | V |
Phase | 1 | ~ |
Frequency | 60 | Hz |
Optional frequency | 50 | Hz |
Power | 80 | W |
Current | 0.35 | A |
Speed | 2810 | r.p.m. |
Max. temperature of transported air | 65 | °C |
Max. temperature of transported air when speed controlled | 65 | °C |
Sound pressure level at 3 m | 37 | dB(A) |
Weight | 11.7 | kg |
Enclosure class | 44 | IP |
Insulation class, motor | F | |
Capacitor | 2 | µF |
Duct connection | 160 | mm |
Max. flow @ 0Pa | 135 | l/s |
Max. pressure | 560 | Pa |
Voltage range | 220-240 | V |