| 8010502 - | HERU 100 LP EC 2AL | 8010500 - | HERU 100 LP EC 2A |
Generating diagrams...
Generating diagrams...
|
HERU 100 LP EC 2AL 8010502 |
HERU 100 LP EC 2A 8010500 |
|||
|---|---|---|---|---|
| Parameter | Value | Unit | Value | Unit |
| Voltage | 230 | V | 230 | V |
| Phase | 1 | ~ | 1 | ~ |
| Frequency | 50 | Hz | 50 | Hz |
| Power | 1170 | W | 1170 | W |
| Power, fans | 245 | W | 245 | W |
| Power, heater | 900 | W | 900 | W |
| Current | 5.99 | A | 5.99 | A |
| Current, fans | 1.98 | A | 1.98 | A |
| Current, heater | 3.91 | A | 3.91 | A |
| Speed | 2850 | r.p.m. | 2850 | r.p.m. |
| Sound pressure level at 3 m | 47 | dB(A) | 47 | dB(A) |
| Weight | 42 | kg | 42 | kg |
| Enclosure class | 41 | IP | 41 | IP |
| Duct connection | 125 | mm | 125 | mm |
| Max. flow @ 0Pa | 104 | l/s | 104 | l/s |
| Max. pressure | 525 | Pa | 525 | Pa |
| Voltage range | 220-240 | V | 220-240 | V |
| Parameter | Value | Unit |
|---|---|---|
| (a) Manufacturer | Östberg | - |
| (b) Model code | HERU 100 LP EC | - |
| (c) SEC value | -34.6 | kWh/m2 |
| SEC class | A | - |
| (d) Declared type | RVU / BVU | - |
| (e) Type of drive | Variable speed drive | - |
| (f) Type of heat recovery | Regenerative | - |
| (g) Thermal efficiency | 82 | % |
| (h) Max. flow rate (@100Pa) | 342 | m3/h |
| (i) Power at max. flow rate | 240 | W |
| (j) Sound power level | 49 | dB LwA |
| (k) Reference flow rate | 0.069 | m3/s |
| (l) Reference pressure difference | 50 | Pa |
| (m) SPI | 0.40 | W/(m3/h) |
| (n) Type of control/ctrl factor | Central demand control | - |
| (o) External (and internal) leakage rate | 2.25 (N/A) | % |
| (p) Mixing rate | N/A | - |
| (q) Visual filter warning | In remote control | - |
| (r) Instruction supply/exhaust grilles | N/A | - |
| (s) Disassembly instructions | www.ostberg.com | - |
| (t) Airflow sensitivity | N/A | - |
| (u) Air tightness | N/A | m/s |
| (v) AEC | 948 | kWh |
| (w) AHS average | 4457 | kWh |
| AHS warmer | 2016 | kWh |
| AHS colder | 8720 | kWh |