| 8010721 - | HERU 100 S EC 2 C | 8010719 - | HERU 100 S EC 2 A | 8010720 - | HERU 100 S EC 2 B |





HERU®100 S EC
NOTE!
The warranty of HERU® is only valid if accessories/equipment (e.g.
filters) from H. Östberg AB are used.
Generating diagrams...
Generating diagrams...
|
HERU 100 S EC 2 C 8010721 |
HERU 100 S EC 2 A 8010719 |
HERU 100 S EC 2 B 8010720 |
||||
|---|---|---|---|---|---|---|
| Parameter | Value | Unit | Value | Unit | Value | Unit |
| Voltage | 230 | V | 230 | V | 230 | V |
| Phase | 1 | ~ | 1 | ~ | 1 | ~ |
| Frequency | 50 | Hz | 50 | Hz | 50 | Hz |
| Power | 236 | W | 1440 | W | 836 | W |
| Power, fans | 209 | W | 209 | W | 209 | W |
| Power, heater | 0 | W | 1200 | W | 600 | W |
| Current | 1.77 | A | 6.99 | A | 4.38 | A |
| Current, fans | 1.67 | A | 1.67 | A | 1.67 | A |
| Current, heater | 0 | A | 5.22 | A | 2.61 | A |
| Speed | 3580 | r.p.m. | 3580 | r.p.m. | 3580 | r.p.m. |
| Sound pressure level at 3 m | 41 | dB(A) | 41 | dB(A) | 41 | dB(A) |
| Weight | 63.5 | kg | 64.8 | kg | 65.2 | kg |
| Enclosure class | 41 | IP | 41 | IP | 41 | IP |
| Duct connection | 160 | mm | 160 | mm | 160 | mm |
| Max. flow @ 0Pa | 113 | l/s | 113 | l/s | 113 | l/s |
| Max. pressure | 710 | Pa | 710 | Pa | 710 | Pa |
| Voltage range | 220-240 | V | 220-240 | V | 220-240 | V |
| Parameter | Value | Unit |
|---|---|---|
| (a) Manufacturer | Östberg | - |
| (b) Model code | HERU 100 S EC 2 | - |
| (c) SEC value | -38.54 | kWh/m2 |
| SEC class | A | - |
| (d) Declared type | RVU / BVU | - |
| (e) Type of drive | Variable speed drive | - |
| (f) Type of heat recovery | Regenerative | - |
| (g) Thermal efficiency | 84% | % |
| (h) Max. flow rate (@100Pa) | 360 | m3/h |
| (i) Power at max. flow rate | 207 | W |
| (j) Sound power level | 48 | dB LwA |
| (k) Reference flow rate | 0.084 | m3/s |
| (l) Reference pressure difference | 50 | Pa |
| (m) SPI | 0.50 | W/(m3/h) |
| (n) Type of control/ctrl factor | Local demand control | - |
| (o) External (and internal) leakage rate | 1.09 (2.80) | % |
| (p) Mixing rate | N/A | - |
| (q) Visual filter warning | In remote control | - |
| (r) Instruction supply/exhaust grilles | N/A | - |
| (s) Disassembly instructions | www.ostberg.com | - |
| (t) Airflow sensitivity | N/A | - |
| (u) Air tightness | N/A | m/s |
| (v) AEC | 309 | kWh |
| (w) AHS average | 4590 | kWh |
| AHS warmer | 2075 | kWh |
| AHS colder | 8979 | kWh |