8010721 - | HERU 100 S EC 2 C | 8010719 - | HERU 100 S EC 2 A | 8010720 - | HERU 100 S EC 2 B |
HERU®100 S EC
NOTE!
The warranty of HERU® is only valid if accessories/equipment (e.g.
filters) from H. Östberg AB are used.
HERU 100 S EC 2 C 8010721 |
HERU 100 S EC 2 A 8010719 |
HERU 100 S EC 2 B 8010720 |
||||
---|---|---|---|---|---|---|
Parameter | Value | Unit | Value | Unit | Value | Unit |
Voltage | 230 | V | 230 | V | 230 | V |
Phase | 1 | ~ | 1 | ~ | 1 | ~ |
Frequency | 50 | Hz | 50 | Hz | 50 | Hz |
Power | 236 | W | 1440 | W | 836 | W |
Power, fans | 209 | W | 209 | W | 209 | W |
Power, heater | 0 | W | 1200 | W | 600 | W |
Current | 1.77 | A | 6.99 | A | 4.38 | A |
Current, fans | 1.67 | A | 1.67 | A | 1.67 | A |
Current, heater | 0 | A | 5.22 | A | 2.61 | A |
Speed | 3580 | r.p.m. | 3580 | r.p.m. | 3580 | r.p.m. |
Sound pressure level at 3 m | 41 | dB(A) | 41 | dB(A) | 41 | dB(A) |
Weight | 63.5 | kg | 64.8 | kg | 65.2 | kg |
Enclosure class | 41 | IP | 41 | IP | 41 | IP |
Duct connection | 160 | mm | 160 | mm | 160 | mm |
Max. flow @ 0Pa | 113 | l/s | 113 | l/s | 113 | l/s |
Max. pressure | 710 | Pa | 710 | Pa | 710 | Pa |
Voltage range | 220-240 | V | 220-240 | V | 220-240 | V |
Parameter | Value | Unit |
---|---|---|
(a) Manufacturer | Östberg | - |
(b) Model code | HERU 100 S EC 2 | - |
(c) SEC value | -38.54 | kWh/m2 |
SEC class | A | - |
(d) Declared type | RVU / BVU | - |
(e) Type of drive | Variable speed drive | - |
(f) Type of heat recovery | Regenerative | - |
(g) Thermal efficiency | 84% | % |
(h) Max. flow rate (@100Pa) | 360 | m3/h |
(i) Power at max. flow rate | 207 | W |
(j) Sound power level | 48 | dB LwA |
(k) Reference flow rate | 0.084 | m3/s |
(l) Reference pressure difference | 50 | Pa |
(m) SPI | 0.50 | W/(m3/h) |
(n) Type of control/ctrl factor | Local demand control | - |
(o) External (and internal) leakage rate | 1.09 (2.80) | % |
(p) Mixing rate | N/A | - |
(q) Visual filter warning | In remote control | - |
(r) Instruction supply/exhaust grilles | N/A | - |
(s) Disassembly instructions | www.ostberg.com | - |
(t) Airflow sensitivity | N/A | - |
(u) Air tightness | N/A | m/s |
(v) AEC | 309 | kWh |
(w) AHS average | 4590 | kWh |
AHS warmer | 2075 | kWh |
AHS colder | 8979 | kWh |