7470057 - | RKB 500x250 C1 ErP |
RKB 500x250 C1 ErP 7470057 |
||
---|---|---|
Parameter | Value | Unit |
Voltage | 230 | V |
Phase | 1 | ~ |
Frequency | 50 | Hz |
Power | 179 | W |
Current | 0.95 | A |
Current when speed controlled | 1.16 | A |
Speed | 1390 | r.p.m. |
Max. temperature of transported air | 60 | °C |
Max. temperature of transported air when speed controlled | 60 | °C |
Sound pressure level at 3 m | 52 | dB(A) |
Weight | 16.9 | kg |
Enclosure class | 54 | IP |
Insulation class, motor | F | |
Capacitor | 3 | µF |
Duct connection | 500x250 | mm |
Max. flow @ 0Pa | 491 | l/s |
Max. pressure | 276 | Pa |
Voltage range | 220-240 | V |
RKB 500x250 C1 ErP 7470057 (50)/60Hz |
||
---|---|---|
Parameter | Value | Unit |
Voltage | 230 | V |
Phase | 1 | ~ |
Frequency | 60 | Hz |
Optional frequency | 50 | Hz |
Power | 271 | W |
Current | 1.2 | A |
Speed | 1580 | r.p.m. |
Max. temperature of transported air | 60 | °C |
Sound pressure level at 3 m | 53 | dB(A) |
Weight | 16.9 | kg |
Enclosure class | 54 | IP |
Insulation class, motor | F | |
Capacitor | 3 | µF |
Duct connection | 500x250 | mm |
Max. flow @ 0Pa | 561 | l/s |
Max. pressure | 385 | Pa |
Voltage range | 220-240 | V |