| 7900077 - | IRE 125 C1 aut tc | 7900006 - |
IRE 125 C1 man tc Archived product |
Generating diagrams...
Generating diagrams...
|
IRE 125 C1 aut tc 7900077 |
IRE 125 C1 man tc 7900006 Archived product |
|||
|---|---|---|---|---|
| Parameter | Value | Unit | Value | Unit |
| Voltage | 230 | V | 230 | V |
| Phase | 1 | ~ | 1 | ~ |
| Frequency | 50 | Hz | 50 | Hz |
| Power | 122 | W | 122 | W |
| Current | 0.53 | A | 0.53 | A |
| Speed | 1850 | r.p.m. | 1850 | r.p.m. |
| Max. temperature of transported air | 50 | °C | 50 | °C |
| Max. temperature of transported air when speed controlled | 50 | °C | 50 | °C |
| Sound pressure level at 3 m | 37 | dB(A) | 37 | dB(A) |
| Weight | 9.7 | kg | 9.7 | kg |
| Enclosure class | 44 | IP | 44 | IP |
| Insulation class, motor | F | F | ||
| Capacitor | 4 | µF | 4 | µF |
| Duct connection | 125 | mm | 125 | mm |
| Max. flow @ 0Pa | 119 | l/s | 119 | l/s |
| Max. pressure | 345 | Pa | 345 | Pa |
| Voltage range | 220-240 | V | 220-240 | V |
| Parameter | Value | Unit |
|---|---|---|
| (a) Manufacturer | Östberg | - |
| (b) Model code | IRE 125 C1 | - |
| (c) SEC average climate | -21.8 | kWh/m2 |
| SEC average climate, class | D | - |
| SEC warm climate | -6.3 | kWh/m2 |
| SEC warm climate, class | F | - |
| SEC cold climate | -48.9 | kWh/m2 |
| SEC cold climate, class | A+ | - |
| (d) Declared type | RVU / UVU | - |
| (e) Type of drive | Multi-speed drive (accessory) | - |
| (f) Type of heat recovery | None | - |
| (g) Thermal efficiency | None | % |
| (h) Max. flow rate (@100Pa) | 377 | m3/h |
| (i) Power at max. flow rate | 118 | W |
| (j) Sound power level | 44 | dB LwA |
| (k) Reference flow rate | 0.073 | m3/s |
| (l) Reference pressure difference | 287 | Pa |
| (m) SPI | 0.39 | W/(m3/h) |
| (n) Type of control/ctrl factor | Local demand control(accessory)/0.65 | - |
| (o) External (and internal) leakage rate | 1.11 (N/A) | % |
| (p) Mixing rate | N/A | - |
| (q) Visual filter warning | N/A | - |
| (r) Instruction supply/exhaust grilles | See manual | - |
| (s) Disassembly instructions | fsp.ostberg.com | - |
| (t) Airflow sensitivity | N/A | - |
| (u) Air tightness | N/A | m/s |
| (v) AEC | 259 | kWh |
| (w) AHS average | 2830 | kWh |
| AHS warmer | 1280 | kWh |
| AHS colder | 5536 | kWh |