| 8000065 - | SAU 200 B3 EC-v1 5kW |




Generating diagrams...
Generating diagrams...
|
SAU 200 B3 EC-v1 5kW 8000065 |
||
|---|---|---|
| Parameter | Value | Unit |
| Cos | 0.55 | |
| Voltage | 400 | V |
| Phase | 3 | ~ |
| Frequency | 50/60 | Hz |
| Power | 5130 | W |
| Power, fans | 122 | W |
| Power, heater | 5000 | W |
| Current | 13.5 | A |
| Current, fans | 0.95 | A |
| Current, heater | 12.5 | A |
| Speed | 2860 | r.p.m. |
| Max. temperature of transported air | 60 | °C |
| Sound pressure level at 3 m | 46 | dB(A) |
| Weight | 26.0 | kg |
| Enclosure class | 44 | IP |
| Insulation class, motor | F | |
| Capacitor | - | µF |
| Duct connection | 200 | mm |
| Max. flow @ 0Pa | 200 | l/s |
| Max. pressure | 628 | Pa |
| Voltage range | 380-415 | V |
| Parameter | Value | Unit |
|---|---|---|
| (a) Manufacturer | Östberg | - |
| (b) Model code | SAU 200 B3 EC | - |
| (c) SEC value | -26.6 | kWh/m2 |
| SEC class | B | - |
| (d) Declared type | RVU / UVU | - |
| (e) Type of drive | Variable speed drive | - |
| (f) Type of heat recovery | N/A | - |
| (g) Thermal efficiency | N/A | % |
| (h) Max. flow rate (@100Pa) | 616 | m3/h |
| (i) Power at max. flow rate | 129 | W |
| (j) Sound power level | 48 | dB LwA |
| (k) Reference flow rate | 0.132 | m3/s |
| (l) Reference pressure difference | 50 | Pa |
| (m) SPI | 0.13 | W/(m3/h) |
| (n) Type of control/ctrl factor | Local demand control | - |
| (o) External (and internal) leakage rate | 1.43 (N/A) | % |
| (p) Mixing rate | N/A | - |
| (q) Visual filter warning | On display | - |
| (r) Instruction supply/exhaust grilles | See manual | - |
| (s) Disassembly instructions | www.ostberg.com | - |
| (t) Airflow sensitivity | N/A | - |
| (u) Air tightness | N/A | m/s |
| (v) AEC | 68 | kWh |
| (w) AHS average | 3018 | kWh |
| AHS warmer | 1365 | kWh |
| AHS colder | 5904 | kWh |