8010796 - | HERU 100 T EC-y1 LE | 8010795 - | HERU 100 T EC-y1 RE |
NOTE! The warranty of HERU is only valid if accessories/equipment (e.g. filters) from H. Östberg AB are used.
HERU 100 T EC-y1 LE 8010796 |
HERU 100 T EC-y1 RE 8010795 |
|||
---|---|---|---|---|
Parameter | Value | Unit | Value | Unit |
Voltage | 230 | V | 230 | V |
Phase | 1 | ~ | 1 | ~ |
Frequency | 50 | Hz | 50 | Hz |
Power | 1410 | W | 1410 | W |
Power, fans | 198 | W | 198 | W |
Power, heater | 1200 | W | 1200 | W |
Current | 6.9 | A | 6.9 | A |
Current, fans | 1.60 | A | 1.60 | A |
Current, heater | 5.22 | A | 5.22 | A |
Speed | 3600 | r.p.m. | 3600 | r.p.m. |
Sound pressure level at 3 m | 41 | dB(A) | 41 | dB(A) |
Weight | 66 | kg | 66 | kg |
Weight (empty casing) | 36.3 | kg | 36.3 | kg |
Enclosure class | 41 | IP | 41 | IP |
Duct connection | 125 | mm | 125 | mm |
Max. flow @ 0Pa | 116 | l/s | 116 | l/s |
Max. pressure | 760 | Pa | 760 | Pa |
Voltage range | 220-240 | V | 220-240 | V |
Parameter | Value | Unit |
---|---|---|
(a) Manufacturer | Östberg | - |
(b) Model code | HERU 100 T EC-y1 | - |
(c) SEC average climate | -41 | kWh/m2 |
SEC average climate, class | A | - |
SEC warm climate | -15.9 | kWh/m2 |
SEC warm climate, class | E | - |
SEC cold climate | -84.9 | kWh/m2 |
SEC cold climate, class | A+ | - |
(d) Declared type | RVU / BVU | - |
(e) Type of drive | Variable speed drive | - |
(f) Type of heat recovery | Regenerative | - |
(g) Thermal efficiency | 84.8 | % |
(h) Max. flow rate (@100Pa) | 378 | m3/h |
(i) Power at max. flow rate | 198 | W |
(j) Sound power level | 45 | dB LwA |
(k) Reference flow rate | 0.073 | m3/s |
(l) Reference pressure difference | 50 | Pa |
(m) SPI | 0.37 | W/(m3/h) |
(n) Type of control/ctrl factor | Local demand control(accessory)/0.65 | - |
(o) External (and internal) leakage rate | 1,99 (3,99) | % |
(p) Mixing rate | N/A | - |
(q) Visual filter warning | In remote control | - |
(r) Instruction supply/exhaust grilles | See manual | - |
(s) Disassembly instructions | fsp.ostberg.com | - |
(t) Airflow sensitivity | N/A | - |
(u) Air tightness | N/A | m/s |
(v) AEC | 194 | kWh |
(w) AHS average | 4586 | kWh |
AHS warmer | 2074 | kWh |
AHS colder | 8971 | kWh |