| 8010822 - | HERU 95 T EC-y1 ALC | 
NOTE! The warranty of HERU is only valid if accessories/equipment (e.g. filters) from H. Östberg AB are used.
 Generating diagrams...
                            
 Generating diagrams...
                            | 
                                                            HERU 95 T EC-y1 ALC 8010822  | 
                                                                                                    ||
|---|---|---|
| Parameter | Value | Unit | 
| Voltage | 230 | V | 
| Phase | 1 | ~ | 
| Frequency | 50 | Hz | 
| Power | 1460 | W | 
| Power, fans | 242 | W | 
| Power, heater | 1200 | W | 
| Current | 7.32 | A | 
| Current, fans | 2.00 | A | 
| Current, heater | 5.22 | A | 
| Speed | 2940 | r.p.m. | 
| Sound pressure level at 3 m | 45 | dB(A) | 
| Weight | 53 | kg | 
| Enclosure class | 41 | IP | 
| Insulation class, motor | F | |
| Duct connection | 125 | mm | 
| Max. flow @ 0Pa | 109 | l/s | 
| Max. pressure | 692 | Pa | 
| Voltage range | 220-240 | V | 
| Parameter | Value | Unit | 
|---|---|---|
| (a) Manufacturer | Östberg | - | 
| (b) Model code | HERU 95 T EC | - | 
| (c) SEC average climate | -39.7 | kWh/m2 | 
| SEC average climate, class | A | - | 
| SEC warm climate | -14.5 | kWh/m2 | 
| SEC warm climate, class | E | - | 
| SEC cold climate | -83.6 | kWh/m2 | 
| SEC cold climate, class | A+ | - | 
| (d) Declared type | RVU / BVU | - | 
| (e) Type of drive | Variable speed drive | - | 
| (f) Type of heat recovery | Regenerative | - | 
| (g) Thermal efficiency | 85.2 | % | 
| (h) Max. flow rate (@100Pa) | 350 | m3/h | 
| (i) Power at max. flow rate | 242 | W | 
| (j) Sound power level | 43 | dB LwA | 
| (k) Reference flow rate | 0.068 | m3/s | 
| (l) Reference pressure difference | 50 | Pa | 
| (m) SPI | 0.47 | W/(m3/h) | 
| (n) Type of control/ctrl factor | Local demand control(accessory)/0.65 | - | 
| (o) External (and internal) leakage rate | 1.99 (3.99) | % | 
| (p) Mixing rate | N/A | - | 
| (q) Visual filter warning | In remote control | - | 
| (r) Instruction supply/exhaust grilles | See manual | - | 
| (s) Disassembly instructions | fsp.ostberg.com | - | 
| (t) Airflow sensitivity | N/A | - | 
| (u) Air tightness | N/A | m/s | 
| (v) AEC | 249 | kWh | 
| (w) AHS average | 4594 | kWh | 
| AHS warmer | 2077 | kWh | 
| AHS colder | 8987 | kWh |