| 004006002 - | HERU Select 500 TRET | 004008002 - | HERU Select 500 TRWT | 004012002 - | HERU Select 500 TRNT | 
                                
                                
                                
                                
                                
                         NOTE! The warranty of HERU is only valid if accessories/equipment (e.g. filters) from H. Östberg AB are used.
 Generating diagrams...
                            
 Generating diagrams...
                            | 
                                                            HERU Select 500 TRET 004006002  | 
                                                                                                            
                                                            HERU Select 500 TRWT 004008002  | 
                                                                                                            
                                                            HERU Select 500 TRNT 004012002  | 
                                                                                                    ||||
|---|---|---|---|---|---|---|
| Parameter | Value | Unit | Value | Unit | Value | Unit | 
| Voltage | 400 | V | 230 | V | 230 | V | 
| Phase | 3 | ~ | 1 | ~ | 1 | ~ | 
| Frequency | 50 | Hz | 50 | Hz | 50 | Hz | 
| Power | 7180 | W | 1176 | W | 1176 | W | 
| Power, fans | 1049 | W | 1049 | W | 1049 | W | 
| Power, heater | 6000 | W | 0 | W | 0 | W | 
| Current | 13.8 | A | 5.17 | A | 5.17 | A | 
| Current, fans | 4.62 | A | 4.62 | A | 4.62 | A | 
| Current, heater | 8.7 | A | 0 | A | 0 | A | 
| Speed | 2390 | r.p.m. | 2390 | r.p.m. | 2390 | r.p.m. | 
| Max. temperature of transported air | 40 | °C | 40 | °C | 40 | °C | 
| Sound pressure level at 3 m | 48 | dB(A) | 48 | dB(A) | 48 | dB(A) | 
| Weight | 318 | kg | 317 | kg | 314 | kg | 
| Enclosure class | 44 | IP | 44 | IP | 44 | IP | 
| Duct connection | 315 | mm | 315 | mm | 315 | mm | 
| Max. flow @ 0Pa | 587 | l/s | 587 | l/s | 587 | l/s | 
| Max. pressure | 1016 | Pa | 1016 | Pa | 1016 | Pa | 
| Voltage range | 380-415 | V | 220-240 | V | 220-240 | V | 
| Parameter | Value | Unit | 
|---|---|---|
| (a) Manufacturer | Östberg | - | 
| (b) Model code | HERU Select 500 | - | 
| (c) Declared type | NRVU / BVU | - | 
| (d) Type of drive | Variable speed drive | - | 
| (e) Type of HRS | Other | - | 
| (f) Thermal efficiency | 85.9 | % | 
| (g) Nominal flow rate | 0.290 | m3/s | 
| (h) Effective power input | 1.030 | kW | 
| (i) SFP int | 496 | W/(m3/s) | 
| (j) Face velocity | 3.72 | m/s | 
| (k) Nominal external pressure | 757 | Pa | 
| (l) Internal pressure drop | 180 | Pa | 
| (n) Static efficiency | 53.7 | % | 
| (o) External (and internal) leakage rate | 0.36 (2.61) | % | 
| (p) Filter classification | D | - | 
| (q) Visual filter warning | In remote control | - | 
| (r) Sound power level | 55 | dB LwA | 
| (s) Disassembly instructions | fsp.ostberg.com | - |