| 8010831 - | HERU 100 T EC-y2 RE | 8010832 - | HERU 100 T EC-y2 LE | 

                                
                                
                                
                                
                                
                                
                                
                                
                         NOTE! The warranty of HERU is only valid if accessories/equipment (e.g. filters) from H. Östberg AB are used. 
 Generating diagrams...
                            
 Generating diagrams...
                            | 
                                                            HERU 100 T EC-y2 RE 8010831  | 
                                                                                                            
                                                            HERU 100 T EC-y2 LE 8010832  | 
                                                                                                    |||
|---|---|---|---|---|
| Parameter | Value | Unit | Value | Unit | 
| Voltage | 230 | V | 230 | V | 
| Phase | 1 | ~ | 1 | ~ | 
| Frequency | 50 | Hz | 50 | Hz | 
| Power | 1410 | W | 1410 | W | 
| Power, fans | 198 | W | 198 | W | 
| Power, heater | 1200 | W | 1200 | W | 
| Current | 6.9 | A | 6.9 | A | 
| Current, fans | 1.60 | A | 1.60 | A | 
| Current, heater | 5.22 | A | 5.22 | A | 
| Speed | 3600 | r.p.m. | 3600 | r.p.m. | 
| Sound pressure level at 3 m | 41 | dB(A) | 41 | dB(A) | 
| Weight | 66 | kg | 66 | kg | 
| Weight (empty casing) | 36.3 | kg | 36.3 | kg | 
| Enclosure class | 41 | IP | 41 | IP | 
| Duct connection | 125 | mm | 125 | mm | 
| Max. flow @ 0Pa | 116 | l/s | 116 | l/s | 
| Max. pressure | 760 | Pa | 760 | Pa | 
| Voltage range | 220-240 | V | 220-240 | V | 
| Parameter | Value | Unit | 
|---|---|---|
| (a) Manufacturer | Östberg | - | 
| (b) Model code | HERU 100 T EC | - | 
| (c) SEC average climate | -41 | kWh/m2 | 
| SEC average climate, class | A | - | 
| SEC warm climate | -15.9 | kWh/m2 | 
| SEC warm climate, class | E | - | 
| SEC cold climate | -84.9 | kWh/m2 | 
| SEC cold climate, class | A+ | - | 
| (d) Declared type | RVU / BVU | - | 
| (e) Type of drive | Variable speed drive | - | 
| (f) Type of heat recovery | Regenerative | - | 
| (g) Thermal efficiency | 84.8 | % | 
| (h) Max. flow rate (@100Pa) | 378 | m3/h | 
| (i) Power at max. flow rate | 198 | W | 
| (j) Sound power level | 45 | dB LwA | 
| (k) Reference flow rate | 0.073 | m3/s | 
| (l) Reference pressure difference | 50 | Pa | 
| (m) SPI | 0.37 | W/(m3/h) | 
| (n) Type of control/ctrl factor | Local demand control(accessory)/0.65 | - | 
| (o) External (and internal) leakage rate | 1,99 (3,99) | % | 
| (p) Mixing rate | N/A | - | 
| (q) Visual filter warning | In remote control | - | 
| (r) Instruction supply/exhaust grilles | See manual | - | 
| (s) Disassembly instructions | fsp.ostberg.com | - | 
| (t) Airflow sensitivity | N/A | - | 
| (u) Air tightness | N/A | m/s | 
| (v) AEC | 194 | kWh | 
| (w) AHS average | 4586 | kWh | 
| AHS warmer | 2074 | kWh | 
| AHS colder | 8971 | kWh |