8010201 - | HERU 130 S EC 2 B 850W | 8010202 - | HERU 130 S EC 2 C | 8010200 - | HERU 130 S EC 2 A 1700W |
│ This product will be discontinued! │
HERU®130 S EC 2
HERU 130 S EC 2 B 850W 8010201 |
HERU 130 S EC 2 C 8010202 |
HERU 130 S EC 2 A 1700W 8010200 |
||||
---|---|---|---|---|---|---|
Parameter | Value | Unit | Value | Unit | Value | Unit |
Voltage | 230 | V | 230 | V | 230 | V |
Phase | 1 | ~ | 1 | ~ | 1 | ~ |
Frequency | 50 | Hz | 50 | Hz | 50 | Hz |
Power | 1210 | W | 355 | W | 2060 | W |
Power, fans | 328 | W | 328 | W | 328 | W |
Power, heater | 850 | W | 0 | W | 1700 | W |
Current | 6.3 | A | 2.59 | A | 10 | A |
Current, fans | 2.49 | A | 2.49 | A | 2.49 | A |
Current, heater | 3.70 | A | 0 | A | 7.39 | A |
Speed | 3080 | r.p.m. | 3080 | r.p.m. | 3080 | r.p.m. |
Sound pressure level at 3 m | 47 | dB(A) | 47 | dB(A) | 47 | dB(A) |
Weight | 85.2 | kg | 83.7 | kg | 85.2 | kg |
Enclosure class | 41 | IP | 41 | IP | 41 | IP |
Duct connection | 200 | mm | 200 | mm | 200 | mm |
Max. flow @ 0Pa | 200 | l/s | 200 | l/s | 200 | l/s |
Max. pressure | 892 | Pa | 892 | Pa | 892 | Pa |
Voltage range | 220-240 | V | 220-240 | V | 220-240 | V |
Parameter | Value | Unit |
---|---|---|
(a) Manufacturer | Östberg | - |
(b) Model code | HERU 130 S EC 2 | - |
(c) SEC value | -39.45 | kWh/m2 |
SEC class | A | - |
(d) Declared type | RVU / BVU | - |
(e) Type of drive | Variable speed drive | - |
(f) Type of heat recovery | Regenerative | - |
(g) Thermal efficiency | 83% | % |
(h) Max. flow rate (@100Pa) | 650 | m3/h |
(i) Power at max. flow rate | 324 | W |
(j) Sound power level | 50 | dB LwA |
(k) Reference flow rate | 0.154 | m3/s |
(l) Reference pressure difference | 50 | Pa |
(m) SPI | 0.42 | W/(m3/h) |
(n) Type of control/ctrl factor | Local demand control | - |
(o) External (and internal) leakage rate | 1.55 (2.80) | % |
(p) Mixing rate | N/A | - |
(q) Visual filter warning | In remote control | - |
(r) Instruction supply/exhaust grilles | N/A | - |
(s) Disassembly instructions | www.ostberg.com | - |
(t) Airflow sensitivity | N/A | - |
(u) Air tightness | N/A | m/s |
(v) AEC | 268 | kWh |
(w) AHS average | 4580 | kWh |
AHS warmer | 2071 | kWh |
AHS colder | 8961 | kWh |