| 8000018 - | SAU 200 B3 man tc |



Generating diagrams...
Generating diagrams...
|
SAU 200 B3 man tc 8000018 |
||
|---|---|---|
| Parameter | Value | Unit |
| Voltage | 400 | V |
| Phase | 3 | ~ |
| Frequency | 50 | Hz |
| Power | 5105 | W |
| Power, fans | 105 | W |
| Power, heater | 5000 | W |
| Current | 11.6 | A |
| Speed | 2500 | r.p.m. |
| Max. temperature of transported air | 40 | °C |
| Sound pressure level at 3 m | 43 | dB(A) |
| Weight | 30.0 | kg |
| Enclosure class | 44 | IP |
| Insulation class, motor | F | |
| Capacitor | 4 | µF |
| Duct connection | 200 | mm |
| Max. flow @ 0Pa | 178 | l/s |
| Max. pressure | 443 | Pa |
| Voltage range | 380-415 | V |
| Parameter | Value | Unit |
|---|---|---|
| (a) Manufacturer | Östberg | - |
| (b) Model code | SAU 200 B3 | - |
| (c) Declared type | NRVU / UVU | - |
| (d) Type of drive | Multi-speed drive | - |
| (e) Type of HRS | N/A | - |
| (f) Thermal efficiency | N/A | % |
| (g) Nominal flow rate | 0.095 | m3/s |
| (h) Effective power input | 0.110 | kW |
| (i) SFP int | N/A | W/(m3/s) |
| (j) Face velocity | 3.0 | m/s |
| (k) Nominal external pressure | 267 | Pa |
| (l) Internal pressure drop | N/A | Pa |
| (n) Static efficiency | 26.2 | % |
| (o) External (and internal) leakage rate | 0.21 | % |
| (p) Filter classification | Efficiency >90% | - |
| (q) Visual filter warning | On label | - |
| (r) Sound power level | 51 | dB LwA |
| (s) Disassembly instructions | www.ostberg.com | - |