| 023025021 - | HERU Select 1000 TRET | 023027021 - | HERU Select 1000 TRWT | 023031021 - | HERU Select 1000 TRNT | 
                                
                                
                                
                                
                                
                         NOTE! The warranty of HERU is only valid if accessories/equipment (e.g. filters) from H. Östberg AB are used.
 Generating diagrams...
                            
 Generating diagrams...
                            | 
                                                            HERU Select 1000 TRET 023025021  | 
                                                                                                            
                                                            HERU Select 1000 TRWT 023027021  | 
                                                                                                            
                                                            HERU Select 1000 TRNT 023031021  | 
                                                                                                    ||||
|---|---|---|---|---|---|---|
| Parameter | Value | Unit | Value | Unit | Value | Unit | 
| Voltage | 400 | V | 400 | V | 400 | V | 
| Phase | 3 | ~ | 3 | ~ | 3 | ~ | 
| Frequency | 50 | Hz | 50 | Hz | 50 | Hz | 
| Power | 13040 | W | 2543 | W | 2543 | W | 
| Power, fans | 2416 | W | 2416 | W | 2416 | W | 
| Power, heater | 10500 | W | 0 | W | 0 | W | 
| Current | 19.5 | A | 4.3 | A | 4.3 | A | 
| Current, fans | 3.75 | A | 3.75 | A | 3.75 | A | 
| Current, heater | 15.2 | A | 0 | A | 0 | A | 
| Speed | 2510 | r.p.m. | 2510 | r.p.m. | 2510 | r.p.m. | 
| Max. temperature of transported air | 40 | °C | 40 | °C | 40 | °C | 
| Sound pressure level at 3 m | 55 | dB(A) | 55 | dB(A) | 55 | dB(A) | 
| Weight | 478 | kg | 476 | kg | 470 | kg | 
| Enclosure class | 44 | IP | 44 | IP | 44 | IP | 
| Duct connection | 400 | mm | 400 | mm | 400 | mm | 
| Max. flow @ 0Pa | 1010 | l/s | 1009 | l/s | 1009 | l/s | 
| Max. pressure | 1429 | Pa | 1429 | Pa | 1429 | Pa | 
| Voltage range | 380-415 | V | 380-415 | V | 380-415 | V | 
| Parameter | Value | Unit | 
|---|---|---|
| (a) Manufacturer | Östberg | - | 
| (b) Model code | HERU Select 1000 | - | 
| (c) Declared type | NRVU / BVU | - | 
| (d) Type of drive | Variable speed drive | - | 
| (e) Type of HRS | Other | - | 
| (f) Thermal efficiency | 86.1 | % | 
| (g) Nominal flow rate | 0.556 | m3/s | 
| (h) Effective power input | 2.170 | kW | 
| (i) SFP int | 449 | W/(m3/s) | 
| (j) Face velocity | 4.42 | m/s | 
| (k) Nominal external pressure | 1031 | Pa | 
| (l) Internal pressure drop | 188 | Pa | 
| (n) Static efficiency | 63.0 | % | 
| (o) External (and internal) leakage rate | 0.27 (3.39) | % | 
| (p) Filter classification | D | - | 
| (q) Visual filter warning | In remote control | - | 
| (r) Sound power level | 62 | dB LwA | 
| (s) Disassembly instructions | fsp.ostberg.com | - |