| 8010840 - | HERU 300 T EC-y2 RE | 8010841 - | HERU 300 T EC-y2 LE |

NOTE! The warranty of HERU is only valid if accessories/equipment (e.g. filters) from H. Östberg AB are used.
Generating diagrams...
Generating diagrams...
|
HERU 300 T EC-y2 RE 8010840 |
HERU 300 T EC-y2 LE 8010841 |
|||
|---|---|---|---|---|
| Parameter | Value | Unit | Value | Unit |
| Voltage | 230 | V | 230 | V |
| Phase | 2 | ~ | 2 | ~ |
| Frequency | 50 | Hz | 50 | Hz |
| Power | 2880 | W | 2880 | W |
| Power, fans | 563 | W | 563 | W |
| Power, heater | 2300 | W | 2300 | W |
| Current | 14.6 | A | 14.6 | A |
| Current, fans | 4.5 | A | 4.5 | A |
| Current, heater | 10.0 | A | 10.0 | A |
| Speed | 3020 | r.p.m. | 3020 | r.p.m. |
| Sound pressure level at 3 m | 41 | dB(A) | 41 | dB(A) |
| Weight | 140 | kg | 140 | kg |
| Weight (empty casing) | 85.6 | kg | 85.6 | kg |
| Enclosure class | 41 | IP | 41 | IP |
| Duct connection | 250 | mm | 250 | mm |
| Max. flow @ 0Pa | 328 | l/s | 328 | l/s |
| Max. pressure | 824 | Pa | 824 | Pa |
| Voltage range | 220-240 | V | 220-240 | V |
| Parameter | Value | Unit |
|---|---|---|
| (a) Manufacturer | Östberg | - |
| (b) Model code | HERU 300 T EC | - |
| (c) SEC average climate | -42 | kWh/m2 |
| SEC average climate, class | A+ | - |
| SEC warm climate | -16.9 | kWh/m2 |
| SEC warm climate, class | E | - |
| SEC cold climate | -85.9 | kWh/m2 |
| SEC cold climate, class | A+ | - |
| (d) Declared type | RVU / BVU | - |
| (e) Type of drive | Variable speed drive | - |
| (f) Type of heat recovery | Regenerative | - |
| (g) Thermal efficiency | 85 | % |
| (h) Max. flow rate (@100Pa) | 999 | m3/h |
| (i) Power at max. flow rate | 452 | W |
| (j) Sound power level | 41 | dB LwA |
| (k) Reference flow rate | 0.194 | m3/s |
| (l) Reference pressure difference | 50 | Pa |
| (m) SPI | 0.29 | W/(m3/h) |
| (n) Type of control/ctrl factor | Local demand control(accessory)/0.65 | - |
| (o) External (and internal) leakage rate | 1.99 (3.99) | % |
| (p) Mixing rate | N/A | - |
| (q) Visual filter warning | In remote control | - |
| (r) Instruction supply/exhaust grilles | See manual | - |
| (s) Disassembly instructions | fsp.ostberg.com | - |
| (t) Airflow sensitivity | N/A | - |
| (u) Air tightness | N/A | m/s |
| (v) AEC | 155 | kWh |
| (w) AHS average | 4590 | kWh |
| AHS warmer | 2075 | kWh |
| AHS colder | 8979 | kWh |